Lightning & Surge Arrestor 900070

Combined lightning current and surge arrester for use in photovoltaic power supply systems up to 1200 V d.c.

🚚 Shipped within 2-3 business days
📦 R99 for shipping added at checkout
🚘 Pickup (Free) from our premises is also available at checkout

  • For use in PV systems according to IEC 60364-7-712
  • Universally applicable in earthed and unearthed PV systems
  • Prewired type 1 and type 2 combined lightning current and surge arrester for use in photovoltaic generator circuits
  • Fault-resistant Y circuit prevents damage to the surge protective device in case of insulation faults in the generator circuit

*Enquire for pricing

SPD according to EN 50539-11

type 1 + type 2

Max. PV voltage [DC+ -> DC-] (UCPV)

≤ 1200 V

Max. PV voltage [DC+/DC- -> PE] (UCPV)

≤ 1200 V

Short-circuit current rating (I SCPV)

10 kA

Nominal discharge current (8/20 μs) (In)

20 kA

Max. discharge current (8/20 μs) (I max)

40 kA

Total discharge current (8/20 μs) [DC+/DC- -> PE] (I total)

40 kA

Total discharge current (10/350 μs) [DC+/DC- -> PE] (I total)

12.5 kA

Lightning impulse current (10/350 μs) [DC+ -> PE/DC- -> PE] (I imp)

6.25 kA

Voltage protection level [(DC+/DC-) -> PE] (UP)

< 3.8 kV

Voltage protection level [DC+ -> DC-] (UP)

< 3.8 kV

Response time (tA)

≤ 25 ns

Operating temperature range (TU)

-40 °C … +80 °C

Operating state / fault indication

green / red

Number of ports

1

Cross-sectional area (min.)

1.5 mm2 solid / flexible

Cross-sectional area (max.)

35 mm2 stranded / 25 mm2 flexible

For mounting on

35 mm DIN rails acc. to EN 60715

Enclosure material

thermoplastic, red, UL 94 V-0

Place of installation

indoor installation

Degree of protection

IP 20

Dimensions

4 module(s), DIN 43880

Weight

509 g

Customs tariff number (Comb. Nomenclature EU)

85363030

GTIN

6942299504521